CORCOM Series FFA AC Feedthrough Filters

FFA Series - AC Feed Through Filters



Series FFA Schematic:
Offer reliability and performance in high frequency applications.
Designed to meet EN132400 safety requirements
Custom designs available where special packaging, mounting, terminations, or multiple lines are required
RoHS compliant

Rated Voltage (max):250 VAC 50/60 Hz
Rated Current: 10 to 300 amps
Test Voltage (two seconds): 5000 VDC
Capacitor Class (EN132400): Designed to meet Y2
Pulse Test (EN132400): 5000V Peak
   Insulation Resistance (within 1 minute)
For C <0.33µF:R> 15000MΩ
For C>0.33µF:RC(MΩ*µF)>5000s
   Operating Ambient Temperature Range (@ rated current Ir)
10 to 100 Amps: -40°C to +60°C
200 Amps: -40°C to +50°C
250 & 300 Amps: -40°C to +40°C
Category Temperature Range: -40°C to +85°C
Climatic Category: 40/85/21
MTBF: Typically >5 million hours
Insulating Materials Flammability Rating: UL 94V-

Filter
ID
Current
Rating
(Amps)
Value
(nF)
Inductance
(nH)
Max.
Leakage
Current
(mA)
DC
Resistance
(MΩ) Max.
Standard Performance
10FFA6-BA102 x 4.7700.96
16FFA6-CA162 x 10701.94
32FFA6-CA322 x 10701.94
63FFA6-GB632 x 47808.93
100FFA6-HC1002 x 10090192
200FFA6-HD2002 x 100120191
250FFA6-HF2502 x 10016019<1
300FFA6-HF3002 x 10016019<1
High Performance
10FFA6-CE102 x 101401.97
16FFA6-DG162 x 221704.24
32FFA6-DH322 x 221804.24
63FFA6-JK632 x 150240293
100FFA6-NP1002 x 47024089<2
200FFA6-NP2002 x 47033089<2
250FFA6-NP2502 x 47033089<2
300FFA6-NP3002 x 47033089<2
Extended Performance
10FFA6-GJ102 x 472108.99
16FFA6-HN162 x 100250196
32FFA6-HN322 x 100250196
63FFA6-NP632 x 47033089<2
100FFA6-PP1002 x 1000330188<2
200FFA6-PP2002 x 1000330188<2
250FFA6-PP12502 x 1000330188<2
300FFA6-PP3002 x 1000330188<2
All units are stud-mounted (see PDF for dimensions)